NEC Table 430.250: motor full-load current
Motor questions follow the same order on every exam: look up the table current, size the branch-circuit conductors, then the short-circuit and ground-fault protection, then the overloads. Only the overloads use the nameplate current.
A timed 80-question exam in the ICC R17 format on the 2023 NEC, or your state’s exact format. Every answer has a worked explanation.
Or start with the free motors and transformers drillThree-phase full-load current: Table 430.250
| Horsepower | 208 V | 230 V | 460 V |
|---|---|---|---|
| 5 | 16.7 | 15.2 | 7.6 |
| 7-1/2 | 24.2 | 22 | 11 |
| 10 | 30.8 | 28 | 14 |
| 15 | 46.2 | 42 | 21 |
| 20 | 59.4 | 54 | 27 |
| 25 | 74.8 | 68 | 34 |
| 30 | 88 | 80 | 40 |
| 40 | — | — | 52 |
| 50 | — | — | 65 |
The four sizing steps
- Use the table current, not the nameplate, for conductors and short-circuit protection (430.6(A)(1)).
- Branch-circuit conductors: at least 125% of the table current (430.22).
- Short-circuit and ground-fault protection: Table 430.52 percentages, for example 250% for an inverse-time breaker and 175% for a dual-element time-delay fuse. When the result is not a standard size, the next larger standard size is permitted (430.52(C)(1) Exception No. 1, 240.6(A)).
- Overload protection: 125% of the nameplate current for motors with a service factor of 1.15 or more or a temperature rise of 40°C or less; 115% for all other motors (430.32(A)(1)).
Worked example
20 hp, 460 V, three-phase motor on an inverse-time breaker
- Table 430.250: 27 A.
- Conductors: 27 × 1.25 = 33.75 A. 10 AWG copper at 75°C is rated 35 A (Table 310.16), so 10 AWG.
- Breaker: 27 × 2.50 = 67.5 A. The next standard size is 70 A.
- Overload with a 25 A nameplate and a 1.15 service factor: 25 × 1.25 = 31.25 A.
Practice motor calculations on a timed exam
A timed 80-question exam in the ICC R17 format on the 2023 NEC, or your state’s exact format. Every answer has a worked explanation.
Or start with the free motors and transformers drillSeveral motors on one feeder
Feeder conductors for several motors must carry 125% of the largest motor full-load current plus the sum of the other motors (430.24). For three 460 V motors of 10, 15 and 20 hp: 27 × 1.25 + 21 + 14 = 68.75 A.
Common questions
Do I use the nameplate or Table 430.250 current?
Use Table 430.250 for conductors and short-circuit protection, and the nameplate current for overload protection (430.6(A)).
What size breaker for a motor?
Multiply the table current by 250% for an inverse-time breaker (Table 430.52). If the result is not a standard size, you may use the next larger standard size.
What is the full-load current of a 10 hp 460 V three-phase motor?
14 amperes (Table 430.250).