NEC conduit fill: chart and calculation

Conduit fill questions ask how many conductors fit in a raceway, or which raceway size a group of conductors needs. Every answer comes from Chapter 9: Table 1 sets the percentage, Table 4 gives the raceway area and Table 5 gives each conductor area.

A timed 80-question exam in the ICC R17 format on the 2023 NEC, or your state’s exact format. Every answer has a worked explanation.

Or start with the free box and conduit fill drill

Watch worked examples, step by step

The 314.16 box fill and Chapter 9 conduit fill methods, worked through 11 questions.

Fill percentage: Chapter 9, Table 1

Maximum percent of raceway area
Number of conductorsMaximum fill
153%
231%
Over 240%

Equipment grounding and bonding conductors count toward fill (Note 3). Nipples 24 in. or shorter may be filled to 60% (Note 4).

EMT areas: Chapter 9, Table 4

Electrical metallic tubing
Trade sizeTotal area (in²)40% area (in²)
1/20.3040.122
3/40.5330.213
10.8640.346
1-1/41.4960.598
1-1/22.0360.814
23.3561.342

THHN and THWN-2 areas: Chapter 9, Table 5

Approximate conductor area
Size (AWG)Area (in²)
140.0097
120.0133
100.0211
80.0366
60.0507
40.0824
30.0973
20.1158
10.1562
1/00.1855

Practice conduit fill on a timed exam

A timed 80-question exam in the ICC R17 format on the 2023 NEC, or your state’s exact format. Every answer has a worked explanation.

Or start with the free box and conduit fill drill

Worked examples

How many 12 AWG THHN fit in 3/4 in. EMT?

  1. More than two conductors, so 40% fill applies. 3/4 in. EMT 40% area = 0.213 in².
  2. 12 AWG THHN area = 0.0133 in².
  3. 0.213 ÷ 0.0133 = 16.0, so 16 conductors.

Sizing a raceway for mixed conductors

Three 6 AWG and one 10 AWG THHN in EMT

  1. Area: 3 × 0.0507 + 1 × 0.0211 = 0.1732 in².
  2. More than two conductors: compare with the 40% column.
  3. 3/4 in. EMT allows 0.213 in², so 3/4 in. is the minimum size.

Rounding: Note 7

When every conductor is the same size, Note 7 to Table 1 lets you round a result of 0.8 or more up to the next whole number. A result below 0.8 is rounded down. For mixed sizes, compare total area with the allowed area instead.

Informative Annex C lists the same-size answers for each raceway type, so you can check a calculation quickly during an open-book exam.

Common questions

What is the maximum conduit fill for three or more wires?

40% of the raceway area (Chapter 9, Table 1).

Do ground wires count in conduit fill?

Yes. Equipment grounding and bonding conductors are included in the fill calculation (Chapter 9, Note 3).

Where do I find how many wires fit in a conduit?

Informative Annex C gives the maximum number of same-size conductors for each raceway type and size.